101BExtended instructions
8.9 Common error codes for the "Extended" instructions
S7-1200 Programmable controller
System Manual, 11/2011, A5E02486680-05
313
8.9
Common error codes for the "Extended" instructions
Table 8- 143 Common condition codes for the extended instructions
Condition code (W#16#....)
1
Description
8022
Area too small for input
8023
Area too small for output
8024
Illegal input area
8025
Illegal output area
8028
Illegal input bit assignment
8029
Illegal output bit assignment
8030
Output area is a read-only DB.
803A
DB does not exist.
1
If one of these errors occurs when a code block is executed the the CPU goes to STOP mode, unless you use the