103BCommunication
10.2 PROFINET
S7-1200 Programmable controller
System Manual, 11/2011, A5E02486680-05
419
ERROR
STATUS
Description
0
7001
Start of job processing, data being sent (TUSEND): During this processing, the
operating system accesses the data in the DATA send area.
Block is ready to receive, receive job was activated (TURCV).
0
7002
Follow-on instruction execution (REQ irrelevant), job being processed (TUSEND):
During this processing, the operating system accesses the data in the DATA send
area.
Follow-on instruction execution, job being processed: During this processing, the
TURCV instruction writes data to the receive area. For this reason, an error could
result in inconsistent data in the receive area.
1
8085
LEN parameter is greater than the largest permitted value, has the value 0 (TUSEND),
or you changed the value of the LEN or DATA parameter since the first instruction
execution (TURCV).
1
8086
The ID parameter is not in the permitted address range.
1
8088
LEN parameter is larger than the memory area (TUSEND) or receive area (TURCV)
specified in DATA.
Receive area is too small (TURCV).
1
8089
ADDR parameter does not point to a data block.
1
80A1
Communications error:
The specified connection between user program and communications layer of the
operating system has not yet been established.
The specified connection between the user program and the communication layer of
the operating system is currently being terminated. Transmission (TUSEND) or a
receive job (TURCV) over this connection is not possible.
The interface is being reinitialized.
1
80A4
IP address of the remote connection end point is invalid; it is possible that it matches
the local IP address (TUSEND).
1
80B3
The set protocol variant (connection_type parameter in the connection description)
is not UDP. Please use the TSEND or TRCV instruction.
ADDR parameter: Invalid settings for port number (TUSEND)
1
80C3
A block with this ID is already being processed in a different priority class.
Internal lack of resources
1
80C4
Temporary communications error:
The connection between the user program and the communication level of the
operating system cannot be established at this time (TUSEND).
The interface is receiving new parameters (TUSEND).
The connection is currently being reinitiated (TURCV).