Operating the contactor panel with panel width 600 mm
110-0134.9 / 14
NXAIR /
≤ 40 kA
155
Procedure
NOTICE
Maloperation
All interlocks are only released when the contactor truck is in a stable end
position.
Rack the contactor truck absolutely until end position.
To release the actuating opening for the double-bit key, lift the operating slide and hold it.
To release access to the contactor truck, insert the double-bit key and turn clockwise as far
as it will go (that is
90°).
Fig. 269: Lifting operating slide and
turning the double-bit key
clockwise
Fig. 270: Operating shaft for
racking crank
Push the racking crank for moving the contactor truck onto the operating shaft, and turn
clockwise as far as it will go.
Remove the racking crank for moving the contactor truck.