Operating the busbar connection panel type I
206
NXAIR /
≤ 40 kA
110-0134.9 / 14
NOTICE
Undetected damage
A tripped protection fuse-link can cause hidden damages on the other protection
fuse-links.
Always replace all protection fuse-links, even if only one protection fuse-
link has tripped.
Selection table for protection fuse-links:
Rated voltage U
r
[kV]
Supplier:
Order details:
7.2
Bussmann
(a business of Eaton)
7.2ABWNA / 3.15 A / 142 mm
12
Bussmann
(a business of Eaton)
12ABCNA / 3.15 A / 195 mm
17.5
Bussmann
(a business of Eaton)
17.5CAV2 / 2 A / 220 mm
Supplier information:
www.eaton.com
Preconditions
•
Withdrawable metering part / metering truck in test position
•
Padlock (optional) removed from door handle
•
High-voltage door open
•
All voltage transformer MCBs switched to OPEN position
•
Low-voltage connector stowed away
•
Withdrawable metering part / metering truck taken out of the panel
•
Set of proper protection fuse-links available
Replacing protection fuse-links for rated voltage
≤ 12 kV
Fig. 367: Withdrawable metering part,
taken out of the panel
(1) Removable protection fuse-link
(2)
Fixed-mounted voltage
transformer
1
2