Operating the contactor panel with panel width 600 mm
200
NXAIR /
≤ 40 kA
110-0134.9 / 14
Permissible protection fuse-links
NOTICE
Maloperation
Contactor trucks are exclusively designed for operation with specific protection
fuse-links for the control transformer.
Use only the fuse-link types listed in the following table.
Do not mount bridging links instead of protection fuse-links.
Rated voltage U
r
[kV]
Supplier
Order details
7.2
Bussmann
(a business of Eaton)
7.2ABWNA / 3.15 A / 142 mm
Supplier information:
www.eaton.com
Removing protection fuse-links for the control transformer
NOTICE
Undetected damage
A tripped protection fuse-link for the control transformer can cause hidden
damages on the other protection fuse-links.
Always replace all protection fuse-links for the control transformer, even if
only one protection fuse-link has tripped.
Preconditions
•
Set of proper protection fuse-links for the control transformer available
•
Contactor truck taken out of the panel
•
HV HRC fuse-links removed from the outer phases (1) and available
•
High-voltage door closed
Fig. 357: HV HRC fuse-links removed from the
outer phases
1