Operating the shutters
296
NXAIR /
≤ 40 kA
110-0134.9 / 14
Fig. 547: Shutter to the connection compartment open
✓
The shutter to the connection compartment is open.
INFORMATION
Final procedure steps
Immediately proceed to perform a voltage test with recommended suitable
equipment or other intended operations.
Closing the shutter to the connection
compartment (lower shutter)
NOTICE
Maloperation
Risk of damaging safety-relevant parts.
Remove the padlock
before
inserting the contactor truck in the switching-
device compartment.
Release the latching rod (2). To do so, hold the latching rod by the handle (3) and move it in
a semi-circular way as shown. Let the slip-on lever slip downwards. The shutter closes.
Fig. 548: Releasing the latching rod
Remove the slip-on lever.
3
2