Accessing the connection compartment through the front
110-0134.9 / 14
NXAIR /
≤ 40 kA
327
Fig. 604: Front part of ventilation duct,
seen from center-right
Fig. 605: Front part of ventilation duct,
seen from center-left
To get the front part of the ventilation duct over the door threshold, lift it approx. 2 cm. Pull it
out of the panel, and store it.
Fig. 606: Lifting and pulling the front part
Remove the connecting elements from the remaining part of the ventilation duct (4) and the
vertical partition to the connection compartment (5), and store it:
•
13 bolts M8x20 with contact washers and plain washers size 8
acc. to ISO 7093 (6)
•
7 bolts M8x20 with contact washers (7)
3