Operating the switch-disconnector panel
238
NXAIR /
≤ 40 kA
110-0134.9 / 14
Fig. 423: The position of the striker
Proceed in the same way with the other HV HRC fuse-links.
✓
The HV HRC fuse-links have been replaced.
INFORMATION
Final procedure steps
Now the panel can be integrated into the course of operation again, for example:
Close the high-voltage door.
Switch the feeder earthing switch to OPEN position.
Insert the operating lever in the actuating opening of the switch-fuse
combination.
Turn the operating lever completely to the end position and switch strongly
towards the OPEN position again. This makes the toggle fastener latch
tight again and the switch-fuse combination can now be closed.
Close the switch-fuse combination.