Accessing the connection compartment through the rear
352
NXAIR /
≤ 40 kA
110-0134.9 / 14
Contactor panels with panel width 435 mm only:
Remove the connecting elements from one of the vertical ledges (1):
•
15 bolts M8x20 with contact washers
Remove the vertical ledge, and store it together with the associated connecting elements.
Proceed in the same way with the other vertical ledge.
(1) Vertical ledges
Fig. 651: Contactor panels with panel width 435 mm only:
30 bolts on ledges
Remove the sealing brackets (2) and store them.
(2) Sealing brackets
Fig. 652: Contactor panels with panel width 435 mm only:
Removing the sealing brackets
Remove the connecting elements from the rear wall:
•
3 bolts M8x20 with contact washers (3)
1
2