Operating the contactor panel with panel width 600 mm
110-0134.9 / 14
NXAIR /
≤ 40 kA
165
Preconditions
•
Authorization to operate the manual unlocking available
•
Auxiliary voltage for the panel disconnected
•
High-voltage door closed
•
Contactor truck in service position
•
Contactor in CLOSED position or OPEN position
•
Key for padlock available
•
Double-bit key available
•
Racking crank available
Procedure
Make sure to operate the particular contactor panel authorization is given for.
To release the actuating opening for the double-bit key, lift the operating slide and hold it.
Fig. 289: Lifting the operating slide
Insert the double-bit key without turning.
Fig. 290: Double-bit key inserted