Panels with motor operating mechanism control
388
NXAIR /
≤ 40 kA
110-0134.9 / 14
Fit a padlock to the control door and close it.
Fig. 702: Circuit-breaker type 3AE1:
Pulling the handle,
fitting the padlock
Fig. 703: Circuit-breaker type 3AE5:
Pulling the handle,
fitting the padlock
✓
The control door is closed.
27.4 Selecting manual operation for racking
NOTICE
Conflicting operation
The requirement of setting the panel to either local or remote control prevents
operating the panel locally and centrally at the same time.
For any local operations ─ manual or electrical ─ set the panel to local
control, for example by switching the local-remote switch to LOCAL
position.
or
Fig. 704: Access mode indicator for racking: starting point "M" or "T"