Operating the circuit-breaker panel
110-0134.9 / 14
NXAIR /
≤ 40 kA
51
Procedure
NOTICE
Maloperation
All interlocks are only released when the withdrawable circuit-breaker / circuit-
breaker truck is in a stable end position.
Always rack the withdrawable circuit-breaker / circuit-breaker truck
completely up to the end position.
Lift the operating slide and hold it.
To release access to the withdrawable circuit-breaker / circuit-breaker truck, insert the
double-bit key and turn counter-clockwise as far as it will go (that is
90°).
Fig. 70: Lifting the operating slide
Fig. 71: Turning the double-bit key
counter-clockwise
Push the racking crank for moving the withdrawable circuit-breaker / circuit-breaker truck
onto the operating shaft, and turn counter-clockwise as far as it will go.
Remove the racking crank for moving the withdrawable circuit-breaker / circuit-breaker truck.