Operating the contactor panel with panel width 600 mm
110-0134.9 / 14
NXAIR /
≤ 40 kA
163
Procedure
To release the actuating opening for the double-bit key, lift the operating slide and hold it.
Fig. 284: Operating slide lifted
Fig. 285: Double-bit key to turn
To open the contactor manually, insert the double-bit key and turn as far as it will go:
•
Contactor truck in service position:
90° counter-clockwise
•
Contactor truck in test position:
90° clockwise
Fig. 286: Position indicator for contactor in OPEN position
✓
The contactor is open.
INFORMATION
Final procedure steps
You may now go on to insert the crank for racking the contactor truck.
Otherwise remove the double-bit key, push the operating slide down, fit a
padlock (optional) to the operating slide and close it.