Operating the removable voltage transformers
252
NXAIR /
≤ 40 kA
110-0134.9 / 14
Fig. 451: Pulling the service truck back to check interlocking
✓
The service truck is interlocked with the panel.
Moving the removable
voltage transformers onto the service truck
NOTICE
Maloperation
If the removable voltage transformers are not correctly interlocked with the service
truck when moving the service truck away from the panel, the removable voltage
transformers can be seriously damaged.
Move the service truck only if the removable voltage transformers are
interlocked in its end position on the service truck.
Lift the handle of the removable voltage transformers. Keep it lifted and pull the removable
voltage transformers onto the service truck as far as it will go. In the end position, the
removable voltage transformers are automatically interlocked with the service truck.
Fig. 452: Pulling the voltage transformers onto
the service truck
Fig. 453: Automatic interlocking
on service truck