Trouble shooting
110-0134.9 / 14
NXAIR /
≤ 40 kA
429
30.2 Panels with switching-device truck
Interlocking of switching-device truck
Fault
Cause
Remedy
Switching-device truck cannot be
pushed completely into the panel
and interlocked.
Positions of feeder earthing switch
operating mechanism (switching-
device truck) and feeder
earthing switch (panel) not in line.
Bring the positions of the
feeder earthing switch
operating mechanism
(switching-device truck) and the
feeder earthing switch (panel)
into line.
Switching-device truck cannot be
pulled out of panel.
Interlocking of switching-device
truck closed.
Open interlocking of switching-
device truck.
High-voltage door cannot be closed.
Low-voltage connector is not
plugged on.
Plug on the low-voltage
connector.
High-voltage door cannot be open.
Switching-device truck is in service
position.
Rack the switching-device truck
to test position.
Switching-device truck
Fault
Cause
Remedy
Actuating opening cannot be open
(switching-device truck cannot be
moved to service position).
Operating lever is inserted in the
manual CLOSE/OPEN operating
mechanism of the feeder
earthing switch.
Remove the operating lever.
Operating slide for opening the
actuating opening is locked.
Open the padlock.
Operating slide for opening the
actuating opening is interlocked by
the electromagnetic interlock.
Request external release.
Double-bit key for releasing the
switching-device truck can be
inserted, but not turned to the right.
Circuit-breaker is in CLOSED
position.
Switch the circuit-breaker to
OPEN position.
Feeder earthing switch is in
CLOSED position.
Switch the feeder
earthing switch to OPEN
position.
High-voltage door is not closed.
Close the high-voltage door.