Panels with motor operating mechanism control
412
NXAIR /
≤ 40 kA
110-0134.9 / 14
27.19 Technical data / operating times
Item
number
Functional unit
Technical data
1.
Voltage supply for
control circuit and motor circuit
Wide-voltage range 24 V DC / 48 V DC / 60 V DC /
110 V DC / 220 V DC / 110 V AC / 230 V AC
Control and motor circuit are executed separately
Voltage fluctuations in the range from 0.85
× U
n
to
1.1
× U
n
are permissible
2.
Power consumption of control circuit
< 100 mA in operating mode
3.
Energizing when the command is given
Until the motor starts up > 180 ms
4.
Power consumption of geared motor for
racking function
110 V DC:
Motor starting current, approx. 6.5 A
Continuous motor current while racking, approx. 1 A
Motor power, approx. 1.2 W
Further values on request.
5.
Motor running time for racking function
< 65 s
6.
Feedback monitoring time for racking
valid switching functions:
Racking to service or test position
After giving the command and when a motor has
started, a fault signal is issued if the feedback
contacts detect no end position within 65 s.
Fault indication and fault evaluation according to
chapter 26.20.