![Siemens NXAIR Скачать руководство пользователя страница 421](http://html.mh-extra.com/html/siemens/nxair/nxair_operating-instructions-manual_380678421.webp)
Service information
110-0134.9 / 14
NXAIR /
≤ 40 kA
421
29.5 Lubricants to be used
CAUTION
Injury due to incorrect application
Incorrect application of the lubricants can cause injuries of the sense organs or the
hands.
Observe the safety instructions in the safety data sheets of the lubricant
suppliers.
Put on personal protective equipment
.
Component
Lubricant
Supplier
Shutter guiding linkage (1)
WD-40 waterproof spray oil
Hardware store
Guide rails (2)
ISOFLEX TOPAS L 32
(Order no.: 3AX1133-3E 1 kg)
www.klueber.com
Fixed contacts of feeder
earthing switch (3)
MOLYKOTE® LONGTERM 2
PLUS EXTREME PRESSURE
BEARING GREASE
(Order no.: 8BX1022 1 kg)
www.dowcorning.com
Main fixed contacts of bushings (4)
Fixed contacts of the switch-fuse
combination
(5)
Fig. 746: Circuit-breaker, disconnecting, metering
and contactor panels
(panel width 600 mm)
Fig. 747: Contactor panel with panel width 435 mm
(1) Shutter guiding linkage
(2) Guide rails
(3)
Fixed contacts of the feeder
earthing switch
(4) Fixed contacts of the bushings
(2)
Fixed contacts of the feeder
earthing switch
(3) Fixed contacts of the bushings