Panels with motor operating mechanism control
110-0134.9 / 14
NXAIR /
≤ 40 kA
387
Preconditions
•
Withdrawable circuit-breaker / circuit-breaker truck in service position or in test position
•
Panel set to local control
•
High-voltage door closed
Procedure
Open the padlock at the control door and remove it.
Pull the handle of the control door upwards, and open the door to the right.
Fig. 700: Circuit-breaker type 3AE1:
Removing the padlock,
pulling the handle
Fig. 701: Circuit-breaker type 3AE5:
Removing the padlock,
pulling the handle
✓
The control door is open.
27.3 Closing the control door
NOTICE
Maloperation
The panel automatically blocks electrical racking when the control door is open.
To prevent accidentally blocking access for electrical racking by opening
the control door, padlock the control door immediately after closing it.
Preconditions
•
High-voltage door open or closed
•
Padlock for control door available
Procedure
Pull the handle upwards and hold it.
Press the control door totally against the high-voltage door.
Push the handle downwards as far as it will go.