Earthing and de-earthing the busbar system
274
NXAIR /
≤ 40 kA
110-0134.9 / 14
NOTICE
Maloperation
If the operating lever is not inserted correctly, the busbar earthing switch may be
damaged.
Insert the operating lever in the actuating opening as far as it will go.
Instruction label on the door to the low-voltage compartment:
In addition to these instructions, an instruction label on the door to the low-voltage compartment informs
about proper operation of the operating lever for the busbar earthing switch.
Fig. 498: Instruction label on door to the low-voltage compartment
Preconditions
•
Busbar earthing switch in OPEN position
•
Intended opening of the padlock released externally
•
Operating lever available
•
Electrician's ladder available as double-step ladder
•
Electromagnetic interlock (optional) deactivated
•
If a withdrawable part / switching-device truck is inserted in the panel:
•
Withdrawable part / switching-device truck in test position
•
Low-voltage connector plugged on
Fig. 499: Operating lever for operating the
busbar earthing switch
Procedure
Ensure that the intended manual switching operation has been released externally.
Make sure according to the panel number at the panel that the release for manual earthing
of exactly this panel is available.
Position the electrician's ladder correctly in front of the panel.