Operating the contactor panel with panel width 600 mm
110-0134.9 / 14
NXAIR /
≤ 40 kA
175
14.16 Plugging o the low-voltage connector
Preconditions
•
Contactor truck in test position
•
Contactor in OPEN position
•
Auxiliary voltage for the panel disconnected
•
High-voltage door open
•
Low-voltage connector stowed away
Procedure
INFORMATION
In addition to these instructions, an instruction label (1) on the contactor truck
informs about plugging on the low-voltage connector.
Follow the advice on the label to push the longitudinal fastener.
Fig. 313: Instruction label on the contactor truck
Take the low-voltage connector out of the support located underneath the low-voltage
compartment.
Fig. 314: Low-voltage connector stowed away
1