Operating the contactor panel with panel width 600 mm
178
NXAIR /
≤ 40 kA
110-0134.9 / 14
Procedure
Unlocking the contactor truck from the panel
To unlock the contactor truck from the panel frame at the center, turn the two locking levers
at the contactor truck to the outside.
Fig. 319: Unlocking the contactor truck from the panel at the center
To unlock the contactor truck from the panel frame at the bottom, pull the locking bracket (1)
upwards until it latches into the retaining hook.
Fig. 320: Unlocking the contactor truck
at the bottom
Fig. 321: Contactor truck ready to move
Moving the contactor truck out of the panel
CAUTION
Maloperation
The contactor truck is designed exclusively for slow and careful driving on
obstacle-free paths.
Before moving the contactor truck, check the path.
Keep the shunting area and paths free of obstacles and dry.
Remove objects such as small parts, installation material or tools from the
floor in the travel area.
Move the contactor truck only slowly and constantly.
The contactor truck is not suitable for unsteady floor, such as stairs,
deepenings or floor joints.