Operating the shutters
110-0134.9 / 14
NXAIR /
≤ 40 kA
289
Closing the shutter to the connection
compartment (lower shutter)
NOTICE
Maloperation
Risk of damaging safety-relevant parts.
Remove
the
padlock
before
inserting
the
withdrawable part /
switching-device truck in the switching-device compartment.
Push the handle of the slip-on lever slightly to the left (to release the latch) and let it slip
upwards. The shutter closes.
Remove the slip-on lever.
Remove the padlock from the left side in the switching-device compartment.
✓
The shutter to the connection compartment is closed.
22.3 Operating the shutter to the busbar compartment in the contactor panel with panel width 435
mm
The mechanism for operating the shutter to the busbar compartment in the contactor panel with panel width
435 mm is different from the mechanism in the other panel versions.
DANGER
Electric shock
If the busbars in the busbar compartment have not been isolated, the contacts will
be live at operational high voltage.
Always observe the
Five Safety Rules
.
Before
opening the shutter to the busbar compartment:
Put on personal protective equipment.
Isolate and earth the busbars in the busbar compartment.
Verify safe isolation from supply.
Padlock the shutter mechanism on the right side in the switching-device
compartment unless you intend to open the shutter to the connection
compartment, too.
Open the shutter to the busbar compartment
safely
:
Only use the slip-on lever. Never try to open the shutter mechanism
touching it directly.
Always operate the slip-on lever
outside
the panel using the handle.
Always
close the shutter to the busbar compartment:
Before interrupting operations inside the switching-device compartment.
Immediately after completing operations inside the switching-device
compartment.