8000m Series
- 36 -
Function
Code
Function
Descriptions
Minimum
Unit
Factory
Setting
Modifica-
tion Type
F3.08~F
3.09
Reserved
F3.10
Pre-alarm option
when overload
0: Not detect
1: Effective during running and
keep running after alarm
2: Effective during running
and stop after alarm (fault
code:E023)
3: Effective during constant
running and keep running after
alarm
4: Effective during constant
running and stop after alarm
1
○
F3.11
Detecting level of
pre-alarm when
overload
1.0~200.0% (referred to inverter
rated current)
0.10% 150.00%
○
F3.12
Detecting time of
pre-alarm when
overload
0~600s 1s
1s
○
F4 Group: V/F Control Parameters
F4.00 V/F
curve
selection
0: Linear curve
1: User-defined curve
2: 1.3 square torque-step-down
curve
3: 1.7 square torque-step-down
curve
4: 2 square torque-step-down
curve
0
●
F4.01 Torque boost
0.0 %(auto) 0.1%~30.0%
0.10%
1.00%
○
F4.02
Torque boost
cut-off frequency
0.0~50.0% (relative to motor
rated frequency)
0.10% 20.00%
●
F4.03 V/F frequency 1
0.00Hz~F4.05
0.01Hz
0.00Hz
●
Содержание 8000m Series
Страница 1: ...8000m Series Compact AC Drive User Manual Version Code 8000m E 602000600 1705...
Страница 11: ...8000m Series 10 Chapter 1 Introduction to the 8000m series VFD 1 1 Model Description 1 2 Namplate Example...
Страница 20: ...8000m Series 19 2 1 4 Electric Elements and Material Peripheral Electric Elements Connection Diagram...
Страница 150: ...8000m Series 149 8 8 Data Address Table of Function Code...
Страница 151: ...8000m Series 150...
Страница 152: ...8000m Series 151...