![SAJ 8000m Series Скачать руководство пользователя страница 59](http://html1.mh-extra.com/html/saj/8000m-series/8000m-series_user-manual_3527063059.webp)
8000m Series
- 58 -
Select the input channel of master frequency of the VFD. Altogether 8 master
frequency channels are available:
0: digital setting of the panel
The initial value is the value of F0.08 “keypad setting frequency”.
The settings of frequency value of the VFD can be adjusted through
▲
and
▼
key
and the multi-function digital input terminal UP/DOWN terminal.
1: settings by a potentiometer of the panel
2: AVI
Option of AVI is that the frequency is determined by one of the analog input
terminals. A standard VFD unit has 2 analog input terminals, among them AVI is
input by voltage 0
~
10V
;
by using jump line selection, ACI can be chose in the way
of 0
~
10V voltage and 0/4
~
20mA current.
3: Reserved
4: Reserved
5: Reserved
6: Multi-step speed terminals
F0.03
Settings of master frequency source X
Factory Setting
1
Setting Options
0
Digital setting Up/down key
1
Potentiometer of panel
2
AVI terminal
3
Reserved
4
Reserved
5
Reserved
6
Multi-step speed terminals
7
Simple PLC
8
PID
9
Communication interface
Содержание 8000m Series
Страница 1: ...8000m Series Compact AC Drive User Manual Version Code 8000m E 602000600 1705...
Страница 11: ...8000m Series 10 Chapter 1 Introduction to the 8000m series VFD 1 1 Model Description 1 2 Namplate Example...
Страница 20: ...8000m Series 19 2 1 4 Electric Elements and Material Peripheral Electric Elements Connection Diagram...
Страница 150: ...8000m Series 149 8 8 Data Address Table of Function Code...
Страница 151: ...8000m Series 150...
Страница 152: ...8000m Series 151...