8000m Series
- 102 -
F8.04
Deceleration time 2
Factory Setting
Defined by
inverter model
Setting Options
0.1~3600s
F8.05
Acceleration time 3
Factory Setting
Defined by
inverter model
Setting Options
0.1~3600s
F8.06
Deceleration time 3
Factory Setting
Defined by
inverter model
Setting Options
0.1~3600s
F8.07
Acceleration time 4
Factory Setting
Defined by
inverter model
Setting Options
0.1~3600s
F8.08
Deceleration time 4
Factory Setting
Defined by
inverter model
Setting Options
0.1~3600s
For the VFD acceleration and deceleration time, there are F0.18 and F0.19 and the
above-mentioned three pairs of acceleration and deceleration time, all these have
the same definition. Please refer to the descriptions of parameter F0.18 and F0.19.
During the operation of AC drive, acceleration/deceleration time1~4 can be chosen
through combinations of multi-function digital input terminals. For more details,
see the descriptions of function code 21 and 22 for parameter F5.01 to F5.05.
F8.09
Jump frequency 1
Factory Setting
0.00Hz
Setting Options
0.00~F0.10
F8.10
Jump frequency 2
Factory Setting
0.00Hz
Setting Options
0.00~F0.10
F8.11
Jump frequency width
Factory Setting
0.00Hz
Setting Options
0.00~F0.10
If the frequency reference is within the frequency jump range, the actual running
Содержание 8000m Series
Страница 1: ...8000m Series Compact AC Drive User Manual Version Code 8000m E 602000600 1705...
Страница 11: ...8000m Series 10 Chapter 1 Introduction to the 8000m series VFD 1 1 Model Description 1 2 Namplate Example...
Страница 20: ...8000m Series 19 2 1 4 Electric Elements and Material Peripheral Electric Elements Connection Diagram...
Страница 150: ...8000m Series 149 8 8 Data Address Table of Function Code...
Страница 151: ...8000m Series 150...
Страница 152: ...8000m Series 151...