8000m Series
- 61 -
F0.09
Running direction selection
Factory Setting
0
Setting Options
0 Forward
1 Reverse
2
Reverse running prohibited
The turning direction of the motor can be changed through setting options of this
functional code. It is equivalent to adjusting any two lines (U, V, W) of the motor for
changing the turning direction.
Note: The turning direction of electric motor will return to its original state after
initialization of parameters. Please use this very cautiously under the occasion that
the system has finished debugging procedures and any change of the turning
direction of electric motor is prohibited.
F0.10
Max. output frequency
Factory Setting
50.00Hz
Setting Options
10.00
~
600.00Hz
F0.11
Upper limit frequency source selection
Factory Setting
0
Options
0 Keypad
setting
(F0.12)
1
AVI terminal (100% corresponds to the setting
frequency of F0.12)
2 Reserved
3
Multi-step speed terminals (Multi-step speed frequency
setting is the upper limit frequency)
4 Communications
interface
Define the source of the upper limit frequency. The upper limit frequency can come
from keypad settings (F0.12), or from analog inputs. When using an analog input to
set the upper limit frequency, the value of 100% of the analog input is corresponding
to F0.12.
Содержание 8000m Series
Страница 1: ...8000m Series Compact AC Drive User Manual Version Code 8000m E 602000600 1705...
Страница 11: ...8000m Series 10 Chapter 1 Introduction to the 8000m series VFD 1 1 Model Description 1 2 Namplate Example...
Страница 20: ...8000m Series 19 2 1 4 Electric Elements and Material Peripheral Electric Elements Connection Diagram...
Страница 150: ...8000m Series 149 8 8 Data Address Table of Function Code...
Страница 151: ...8000m Series 150...
Страница 152: ...8000m Series 151...