8000m Series
- 86 -
Attached Table 2 Instruction of Acceleration/Deceleration Time
Terminal 2
Terminal 1
Seletion of
accleration/decelerat
ion time
Corresponding
parameters
OFF OFF
Acceleration
time1
F0.18
、
F0.19
OFF
ON
Acceleration
time2
、
F8.03 F8.04
ON
OFF Acceleration
time3
、
F8.05 F8.06
ON
ON
Acceleration
time4
、
F8.07 F8.08
Sensitivity setting of the multi-function digital input terminals: If the digital input
terminals are interfered and result in malfunction in some cases, increase this
parameter setting for better anti-interference, but maybe the terminal sensitivity will
then decrease also.
This parameter defines 4 control modes of VFD by terminal inputs.
0: 2-wire control mode 1. This mode is the most usual one. By terminal command
of M1(FWD) and M2(REV), the motor will run forward or reversed as shown in
the following table and wiring diagram.
F5.10
On/off filter times
Factory Setting
5
Setting Options
1
~
10
F5.11
Terminal control mode
Factory Setting
0
Setting Options
0:2-wire control mode 1
1:2-wire control mode 2
2:3-wire control mode 1
3:3-wire control mode 2
Содержание 8000m Series
Страница 1: ...8000m Series Compact AC Drive User Manual Version Code 8000m E 602000600 1705...
Страница 11: ...8000m Series 10 Chapter 1 Introduction to the 8000m series VFD 1 1 Model Description 1 2 Namplate Example...
Страница 20: ...8000m Series 19 2 1 4 Electric Elements and Material Peripheral Electric Elements Connection Diagram...
Страница 150: ...8000m Series 149 8 8 Data Address Table of Function Code...
Страница 151: ...8000m Series 150...
Страница 152: ...8000m Series 151...