8000m Series
- 122 -
FB.00
Swing frequency range
Factory Setting
0.00%
Setting Options
0.0~100.0% (relative to setting frequency)
FB.01
Skip frequency range
Factory Setting
0.00%
Setting Options
0.0~50.0% (relative to swing frequency
bandwidth)
These parameters are definitions of swing frequency range and skip frequency
range.
The swing operation frequency is keep within bounds of upper and lower limits of
frequency.
Swing amplitude(AW)=Set frequency(Fset)
×
Swing frequency range(FB.00)
Skip frequency range is the percentage of skip frequency to the swing frequency,
as: Skip frequency=swing frequency
×
skip frequency range.
FB.02
Rising time of swing
frequency
Factory Setting
5.0s
Setting Options
0.1~3600.0s
FB.03
Dropping time of swing
frequency
Factory Setting
5.0s
Setting Options
0.1~3600.0s
FB.04
Fixed length control mode
Factory
Setting
0
Setting Options
0
Start from zero when power on
1
Start from record of length of
the last power off
0: VFD starts fixed length control from 0 every time it is power on.
1: VFD starts fixed length control from record of the last power off.
VFD can only starts fixed length control during operation mode, and never starts
during stop mode
Содержание 8000m Series
Страница 1: ...8000m Series Compact AC Drive User Manual Version Code 8000m E 602000600 1705...
Страница 11: ...8000m Series 10 Chapter 1 Introduction to the 8000m series VFD 1 1 Model Description 1 2 Namplate Example...
Страница 20: ...8000m Series 19 2 1 4 Electric Elements and Material Peripheral Electric Elements Connection Diagram...
Страница 150: ...8000m Series 149 8 8 Data Address Table of Function Code...
Страница 151: ...8000m Series 150...
Страница 152: ...8000m Series 151...