8000m Series
- 25 -
2.2.5 Control Circuit Terminals
Symbol
Terminal Name
Function
M1~M4
Multi-functional digital
input terminals
Do not connect additional power source
directly.
A digital input is ON when it is connected to
GND, and will be OFF when it is opened.
Action current is 10mA.
GND
Ground terminal
Zero potential of +10V and +24V
MO1
Multi-functional open
collector output terminal
(Optical coupling isolating)Max. DC
48V/50mA
AVI Analog
input
terminal
Default: Input voltage range DC 0~10V (input
impedance:20k
Ω
)
Option: DC current 0-20mA (Jumper J10)
10V
Analog reference voltage 10V ±5%, Max. current: 30mA
FM
Analog output terminal
Default: DC voltage 0-10V
Option: DC current 4-20mA (Jumper J2)
TA/TB/ TC
Programmable Relay
Output
TA-TB: normally open;
TB-TC: normally closed;
Contact capacity:
AC 250V / 3A/ normally open
AC 250V / 3A / normally closed
+24V
+24V power supply
Output current: Maxi. 200mA, usually used as
power of digital input/output terminals and
external sensor.
2.2.5 Precautions for Connecting Control Circuit Terminals
It is necessary to use shielded cable and twisted pair cable well-grounded (inverter
side). The cable should be more than 20cm away from power electricity cables and
conductors. Do not run the control cable paralleling to power electricity cables, try
vertically.
Содержание 8000m Series
Страница 1: ...8000m Series Compact AC Drive User Manual Version Code 8000m E 602000600 1705...
Страница 11: ...8000m Series 10 Chapter 1 Introduction to the 8000m series VFD 1 1 Model Description 1 2 Namplate Example...
Страница 20: ...8000m Series 19 2 1 4 Electric Elements and Material Peripheral Electric Elements Connection Diagram...
Страница 150: ...8000m Series 149 8 8 Data Address Table of Function Code...
Страница 151: ...8000m Series 150...
Страница 152: ...8000m Series 151...