5.5 F4 Group: V/F Control Parameters
This group of codes are only effective for V/F control(F0.00=1), but are invalid for
vector control.
V/F control is fit for fans,pumps and other general loads, or the situation of one
VFD drives several electric motors, or the situation that the frequency of the VFD
has too much difference with that of the electric motor.
F4.00
V/F curve selection
Factory Setting
0
Setting Options
0 Linear
curve
1 User-defined
curve
2
1.3 square torque-step-down curve
3
1.7 square torque-step-down curve
4
2 square torque-step-down curve
0:Linear curve, suitable for situations of ordinary constant torque load.
1:User-defined curve,suitable for special loads such as water extractor,
hydro-extractor etc.Now by setting the parameters of F F4.03
~
F4.08, you can get
any curve about V/F relations.
2:1.3 square torque-step-down.
3:1.7 square torque-step-down.
4: 2 square torque-step-down curve.
F4.01
Torque boost
Factory Setting
3.0%
Setting Options
0.0 %(auto) 0.1%
~
30.0%
F4.02
Torque boost cut-off frequency
Factory Setting
20.0%
Setting Options
0.0
~
50.0% (relative to motor rated
frequency)
In order to make up for the feature of low-frequency torque of V/F control, do a lift
Содержание 8000m Series
Страница 1: ...8000m Series Compact AC Drive User Manual Version Code 8000m E 602000600 1705...
Страница 11: ...8000m Series 10 Chapter 1 Introduction to the 8000m series VFD 1 1 Model Description 1 2 Namplate Example...
Страница 20: ...8000m Series 19 2 1 4 Electric Elements and Material Peripheral Electric Elements Connection Diagram...
Страница 150: ...8000m Series 149 8 8 Data Address Table of Function Code...
Страница 151: ...8000m Series 150...
Страница 152: ...8000m Series 151...