5.8 F7 Group Display Interface Parameters
F7.00
User
P
assword
Factory Setting
0
Setting Options
0~9999
The password protection will take effect after this parameter is set as a non zero
digit.
0000: Clear the password being set before, and disable password protection;
Restoring factory setting can also clear password.
After password is set and has take effect, if the password isn’t correct, user can not
enter parameter menu display. Only give a correct password to enter parameter
display and edition mode. The password being set must be keep in mind.
Password protection will take effect 1 minute after withdrawing from parameter
edition mode. While the password protection has been enabled, “0.0.0.0” will be
displayed first as the PRGM is pressed for entering parameter edition mode.
Password must be input correctly, or the edition mode will never been enabled.
F7.01~F7.03 Reserved
F7.04
RUN/STOP key stop
function
Factory Setting
0
Setting Options
0:Only valid for keypad setting
1:Valid for both keypad setting and
terminals setting
2:Valid for both keypad setting and
communication interface setting
3:Valid for all control mode
F7.05 Reserved
F7.06
Running status display
Factory Setting
35
Содержание 8000m Series
Страница 1: ...8000m Series Compact AC Drive User Manual Version Code 8000m E 602000600 1705...
Страница 11: ...8000m Series 10 Chapter 1 Introduction to the 8000m series VFD 1 1 Model Description 1 2 Namplate Example...
Страница 20: ...8000m Series 19 2 1 4 Electric Elements and Material Peripheral Electric Elements Connection Diagram...
Страница 150: ...8000m Series 149 8 8 Data Address Table of Function Code...
Страница 151: ...8000m Series 150...
Страница 152: ...8000m Series 151...