8000m Series
- 94 -
F6.09
AM output selection
Factory Setting
0
The signal scope of analog output FM is 0V~10V or 0mA~20mA.
The analog output scope calibration is as following table.
Setting
value
Function
Analog output 0.0%~100.0%
Corresponding value
0
Running frequency
0~Maximun output frequency
1
Setting frequency
0~Maximun output frequency
2
Running rotation
speed
0~Running rotation speed correspond to
maximum output frequency
3
Output current
0~2 times of motor rated current
4
Output voltage
0~1.2 times of VFD rated voltage
5~7 Reserved
8
Analog AVI input
value
0~10V
9~10 Reserved
F6.05
FM output lower limit
Factory Setting
0.0%
Setting Options
0.0~100.0%
F6.06
FM lower limit
corresponding to output
Factory Setting
0.00V
Setting Options
0.00V~10.00V
F6.07
FM output upper limit
Factory Setting
100.0%
Setting Options
0.0~100.0%
F6.08
FM upper limit
corresponding to output
Factory Setting
10.00V
Setting Options
0.00V~10.00V
F6.10~F6.13 Reserved
The above function codes define the corresponding relation between the FM output
range and the analog output signal limits. When the output exceeds the scope
between the defined upper and lower input limits, the analog output signal is
Содержание 8000m Series
Страница 1: ...8000m Series Compact AC Drive User Manual Version Code 8000m E 602000600 1705...
Страница 11: ...8000m Series 10 Chapter 1 Introduction to the 8000m series VFD 1 1 Model Description 1 2 Namplate Example...
Страница 20: ...8000m Series 19 2 1 4 Electric Elements and Material Peripheral Electric Elements Connection Diagram...
Страница 150: ...8000m Series 149 8 8 Data Address Table of Function Code...
Страница 151: ...8000m Series 150...
Страница 152: ...8000m Series 151...