Following is Influences to the corresponding performances while adjusting the
carrier frequency:
Carrier frequency
Low
→
High
Motor noises
Loud
→
Low
Output current waveform
Bad
→
Good
Temperature rise of motor
High
→
Low
Temperature rise of VFD
Low
→
High
Leakage current
Small
→
Large
Exterior radiation interference
Small
→
Large
0
:
PWM mode 1, this mode is a normal PWM mode, when the frequency is low, the
motor noise is low, on the contrary the noise is loud.
1: PWM mode 2, the motor noise is low when the motor runs in this mode, but the
motor temperature rise is high. The rated power of the VFD should be degraded if
this function is chosen.
2: PWM mode 3,the motor noise is loud when the motor runs in this mode, but this
mode has a very good inhibiting effect for electric-mechanic oscillation.
F0.18
Acceleration time 1
Factory Setting
According to model
Setting scope
0.1
~
3600.0s
F0.19
Deceleration time 1
Factory Setting
According to model
Setting scope
0.1
~
3600.0s
Acceleration time 1 means the needed time T1 that the VFD accelerate from 0Hz to
the Max. output frequency(F0.10).
F0.17
PWM mode selection
Factory Setting
0
Setting
Options
0
PWM mode 1
1
PWM mode 2
2
PWM mode 3
Содержание 8000m Series
Страница 1: ...8000m Series Compact AC Drive User Manual Version Code 8000m E 602000600 1705...
Страница 11: ...8000m Series 10 Chapter 1 Introduction to the 8000m series VFD 1 1 Model Description 1 2 Namplate Example...
Страница 20: ...8000m Series 19 2 1 4 Electric Elements and Material Peripheral Electric Elements Connection Diagram...
Страница 150: ...8000m Series 149 8 8 Data Address Table of Function Code...
Страница 151: ...8000m Series 150...
Страница 152: ...8000m Series 151...