8000m Series
- 47 -
Function
Code
Function
Descriptions
Minimum
Unit
Factory
Setting
Modifica-
tion Type
F9.00 PID setting source
0:Keypad (F9.01)
1:Analog terminal AVI
2:Reserved
3:Communication interface
4:Muli-function digital input
terminals
0
○
F9.01 PID preset value
0.0%~100.0%
0.10%
0.00%
●
F9.02
PID feedback
selection
0:Analog terminal AVI
1:Reserved
2:Reserved
3:Communication interface
0
○
F9.03
PID output
characteristic
0: Positive
1: Negative
0
○
F9.04
Proportional gain
(Kp)
0.0~100.0 0.1
0.1
○
F9.05 Integral time (Ti) 0.01~10.00s
0.01s
0.10s
○
F9.06
Differential time
(Td)
0.00~10.00s 0.01s
0.00s
○
F9.07
Sampling period
(T)
0.01~100.0s 0.01s
0.10s
○
F9.08
PID control
deviation limit
0.0~100.0% 0.10%
0.00%
○
F9.09
Feedback loss
detecting time
0.0~100.0% 0.10%
0.00%
○
F9.10
Feedback lost
detecting time
0.0~3600.0s 0.1s
1.0s
○
F9.11
PID sleep function
option
0: PID normal working
1: PID sleep
0
○
F9.12
PID sleep detecting
delay time
0.0~3600.0s 0.1s
3.0s
○
Содержание 8000m Series
Страница 1: ...8000m Series Compact AC Drive User Manual Version Code 8000m E 602000600 1705...
Страница 11: ...8000m Series 10 Chapter 1 Introduction to the 8000m series VFD 1 1 Model Description 1 2 Namplate Example...
Страница 20: ...8000m Series 19 2 1 4 Electric Elements and Material Peripheral Electric Elements Connection Diagram...
Страница 150: ...8000m Series 149 8 8 Data Address Table of Function Code...
Страница 151: ...8000m Series 150...
Страница 152: ...8000m Series 151...