8000m Series
- 124 -
5.13 FC Group RS485 Communication Parameters
FC.00
Local address
Factory Setting
1
Setting Options
0~247
When the master node’s communication frame address is 0, it refers to the
broadcast address, and all the slave nodes will receive this frame but never reply.
Note: The address of slave node cannot be set as 0.
A local node address must be unique among the whole communication network.
This is essential for the peer-to-peer communication between a upper monitor and
VFDs.
FC.01
Baud rate selection
Factory
Setting
3
Setting Options
0 1200BPS
1 2400BPS
2 4800BPS
3 9600BPS
4 19200BPS
5 38400BPS
This parameter is used for setting of data transfer speed between upper monitor
and VFDs. Note: The baud rate settings of upper monitor and VFDs must be
identical, or communication cannot be carried out. The larger the baud rate is, the
faster the communication speed.
FC.02
Data bit check and format
Factory Setting
0
Setting Options
0: No check (N, 8, 1) for RTU
1: Even parity check (E, 8, 1) for RTU
2: Odd parity check (0, 8, 1) for RTU
3: No check (N, 8, 2) for RTU
4: Even parity check (E, 8, 2) for RTU
5: Odd parity check (0, 8, 2) for RTU
FC.03
Communication response
Factory Setting
0
Содержание 8000m Series
Страница 1: ...8000m Series Compact AC Drive User Manual Version Code 8000m E 602000600 1705...
Страница 11: ...8000m Series 10 Chapter 1 Introduction to the 8000m series VFD 1 1 Model Description 1 2 Namplate Example...
Страница 20: ...8000m Series 19 2 1 4 Electric Elements and Material Peripheral Electric Elements Connection Diagram...
Страница 150: ...8000m Series 149 8 8 Data Address Table of Function Code...
Страница 151: ...8000m Series 150...
Страница 152: ...8000m Series 151...