8000m Series
- 46 -
Function
Code
Function
Descriptions
Minimum
Unit
Factory
Setting
Modifica-
tion Type
F8.15
Braking threshold
voltage
115.0~140.0% (Standard DC
bus voltage)
0.10% 120.00%
○
F8.16
Speed display
coefficient
0.1~999.9% 0.10%
100.00%
○
8.17
Option as running
time reached
0:Keep running
1:Stop
0
○
F8.18
Running time
setting
0~9999h 1h
9999
○
F8.19 Droop
control
0.00Hz~10.00Hz
0.01Hz 0.00Hz
○
F8.20
Panel
potentiometer filter
time selection
0.00~10.00s 0.01s
0.10s
○
F8.21
Output delay time
selection
0~9999s 0.1s
0.0s
○
F8.22
Lower limit of
frequency
detecting
0.00~Maxi. Frequency
0.01Hz 20.00Hz
○
F8.23
Upper limit of
frequency
detecting
0.00~Maxi. Frequency
0.01Hz 40.00Hz
○
F8.24 Reserved
F8.25
Inverter rated
power
0.4~700.0kW 0.1kW
Defined
by
inverter
model
◎
F8.26
Inverter rated
current
0.0~2000A 0.1A
◎
F8.27
Linear speed
display coefficient
0.1~ 999.9% (linear speed =
mechanical speed * F8.27)
0.10% 1.00%
○
F8.28 ~
F8.29
Reserved
F9/FE Group PID Control Parameters
Содержание 8000m Series
Страница 1: ...8000m Series Compact AC Drive User Manual Version Code 8000m E 602000600 1705...
Страница 11: ...8000m Series 10 Chapter 1 Introduction to the 8000m series VFD 1 1 Model Description 1 2 Namplate Example...
Страница 20: ...8000m Series 19 2 1 4 Electric Elements and Material Peripheral Electric Elements Connection Diagram...
Страница 150: ...8000m Series 149 8 8 Data Address Table of Function Code...
Страница 151: ...8000m Series 150...
Страница 152: ...8000m Series 151...