![SAJ 8000m Series Скачать руководство пользователя страница 118](http://html1.mh-extra.com/html/saj/8000m-series/8000m-series_user-manual_3527063118.webp)
8000m Series
- 117 -
Setting Options
110~150%
FA.04: As in deceleration process of VFD, by the influence of load inertia, the
motor speed’s deceleration rate might be lower than the frequency reducing rate,
thus it results in power regeneration to VFD by motor and bus voltage increasing.
In some cases with no measure being carried out, it will put the VFD to over
voltage fault due to high bus voltage finally.
For 220V single phase VFD the value of parameter Over-voltage stalling
protection point FA.05 is 120%, and for 380V three-phase VFD this value of
FA.05 is 130%.
The principle of over-voltage stalling protection is as following: By sensing bus
voltage and comparing to FA.05 (relative to standard bus voltage) which defining
the over-voltage stalling point, if the bus voltage is over the point, VFD will stop
decreasing output frequency, and will keep running in current frequency until the
bus voltage falling to lower than the point. And then VFD will continue to
decelerate the motor again. As shown in the following illustration.
Содержание 8000m Series
Страница 1: ...8000m Series Compact AC Drive User Manual Version Code 8000m E 602000600 1705...
Страница 11: ...8000m Series 10 Chapter 1 Introduction to the 8000m series VFD 1 1 Model Description 1 2 Namplate Example...
Страница 20: ...8000m Series 19 2 1 4 Electric Elements and Material Peripheral Electric Elements Connection Diagram...
Страница 150: ...8000m Series 149 8 8 Data Address Table of Function Code...
Страница 151: ...8000m Series 150...
Страница 152: ...8000m Series 151...