in accordance with deceleration mode and the defined acceleration and
deceleration time, and the VFD will stop if the frequency reduced to 0.
1: Coast to stop
After the stop command having taken effect, the VFD immediately ceases to output.
The VFD will coast to stop according to mechanical inertia.
F1.06
Trigging frequency of DC braking at stop
Factory Setting
0.00Hz
Setting Scope
0.00Hz
~
F0.10
F1.07
Waiting time before DC braking at stop
Factory Setting
0.0s
Setting Scope
0.0
~
50.0s
F1.08
DC braking current at stop
Factory Setting
0%
Setting Range
0.0
~
150.0%
F1.09
DC braking time at stop
Factory Setting
0.0s
Setting Range
0.0
~
50.0s
Trigging frequency of DC braking at stop: in the process of deceleration and slowing
down, as soon as the VFD reaches this frequency, it will stop and go into the process
of DC braking.
Waiting time before DC braking at stop: before DC braking, the VFD ceases to
output, after this delay it begins DC braking. This function is used to avoid transient
fault caused by DC braking when the speed is too high.
DC braking current at stop: means the added current of DC braking. The bigger the
current is, the stronger the effect of DC braking. The braking current of the power of
halt is the percentage of rated current of the VFD.
DC braking time at stop: the added time for DC braking. If this value is 0, means
there is no DC braking process, the VFD will stop according to the set deceleration
and halt process.
Содержание 8000m Series
Страница 1: ...8000m Series Compact AC Drive User Manual Version Code 8000m E 602000600 1705...
Страница 11: ...8000m Series 10 Chapter 1 Introduction to the 8000m series VFD 1 1 Model Description 1 2 Namplate Example...
Страница 20: ...8000m Series 19 2 1 4 Electric Elements and Material Peripheral Electric Elements Connection Diagram...
Страница 150: ...8000m Series 149 8 8 Data Address Table of Function Code...
Страница 151: ...8000m Series 150...
Страница 152: ...8000m Series 151...