4. Description of the RPCM Device
Legend:
1
— outlet number;
2
— instant current value;
3
—graph of current and active power;
4
— instant power value;
5
—
"INFORMATION"
values block;
6
—
"COUNTERS"
block with accumulated power consumption counters;;
7
—
"OVERVOLTAGE PROTECTION"
block;
8
—
"ALARM LIMIT"
block;
9
— "
gear
" button to open the "
OUTPUT SETTINGS
" overlay interface;
10
—
"TURN OFF LIMIT"
block.
4.5.5. Setting the Output Parameters
To set the outlet control parameters, use the pop-up window
OUTPUT SETTINGS
To open it, click
on the
gear
button of the corresponding outlet.
List of additional pop-up window settings
OUTLET SETTINGS
:
Name — name of the outlet;
Description
— more detailed description;
don’t turn on automatically after startup
— when voltage is applied to the RPCM after
a complete shutdown, this output will remain off;
turn on after start-up, s
— delay at start-up; set to avoid high in-rush currents and to
start infrastructure in correct order during start-up after power blackout;
survival priority
— priority with which the channels are deactivated in case of a general
overload (highest is 0, lower is 9, the higher the priority, the later the channel is discon-
nected in the event of input overload);
restart delay, s
— timeout between turning off and turning on when power on outlets
restart, up to 65534 seconds max;
overcurrent alarm limit, mA
— maximum permissible current; when exceeded, the sys-
tem initiates alarm condition indication that the limit was exceeded;
overcurrent alarm limit, s
— delay in seconds, after which the alarm is activated;
70