3. Start Setting Up
3.2. System Requirements
3.2.1. Power and Ground Requirements
Power and Ground Requirements for RPCM DC ATS 76A:
voltage -42 - -58VDC;
grounding is required;
input circuit breakers should be easily accessible to disconnect in case of danger.
Power and Ground Requirements for RPCM DC 232A:
voltage -42 - -58VDC;
grounding is required;
input circuit breakers should be easily accessible to disconnect in case of danger.
Note. In order to protect outlets from short circuits, short circuit protection selectivity has to be ensured in the electrical
design. For RPCM DC ATS 76A, RPCM DC 232A — short circuit protection trips at ~87.5A current on the outlet. Short circuit
tripping time – around 100 microseconds. In order to isolate short circuit on individual outlets you should choose circuit
breakers on input that have tripping delay 2 ms or longer.
3.2.2. Computer Requirements for Administration
A physical cable with an RJ45 connector for connecting to an Ethernet-family LAN is needed.
In order to connect and manage via web interface, the following are required:
RAM — 2GB or more;
Minimum network bandwidth (LAN) - 1Mb/s;
A mouse or similar device;
An internet browser.
The RPCM web interface supports various browsers, including:
Chrome — from version 61.0.3163.100;
Safari — from version version 10.1.1;
Firefox — from version version 56.0;
Opera — from version version 48.0.2685.32.
To connect and manage via SSH in command line mode, the following are required:
RAM — 256MB;
Minimum network bandwidth (LAN) - 64Kb/s;
For UNIX-like systems (including Mac OS X), you can use the built-in terminal emulator.
For operating systems belonging to the Windows family, it is recommended to use the free
program PUTTY.
22