6. Command Reference of RPCM CLI
6.8.10.3 Command
set input voltage limit
Use this command for voltage top and bottom limits.
Help ask (also the input number is necessary):
set input 1 voltage ?
The return is:
set input 1-2 voltage limit min - minimum allowed voltage at
specified on input
max - maximum allowed voltage at
specified on input
Type 'help' to get suggestions
Example.
Set voltage limits from 45V to 51V.
Command:
set input 1 voltage limit min 45 max 51
The return is:
Minimum voltage value is set to 45 for Input 1
Maximum voltage value is set to 51 for Input 1
Type 'help' to get suggestions
Type 'help' to get suggestions
6.8.11. Command
set radius server
For changing of RADIUS servers settings.
Required parameters:
ip —
IP of RADIUS server ;
secret key.
Available parameters:
priority <priority>
— numbers from 1 to 100, then more then high priority;
port <port>
— from 1 to 65534;
enabled <yes|no>
;
use-vsa-group <yes|no>
— enable or disable VSA (Vendor-Specific Attributes) answer from
RADIUS server;
use-vsa-session-timeout <yes|no>
— timeout VSA answer from RADIUS server.
297