4. Description of the RPCM Device
Figure 4.2.2. Dashboard in View Mode for RPCM DC ATS 76A.
4.2.3. Description of RPCM's Color Signal System
To quickly obtain information, a color coding of inlets and outlets status is used. Below is a brief
description of the color options.
Description of input color signals:
green
— input is active, voltage within specified ranges;
blue
— input is reserve (for models RPCM with ATS), voltage within specified ranges;
red
— there is no voltage on this input;
gray
— input is administratively disabled;
yellow
— the voltage of the input is outside the specified limits;
blinking from green / blue / red to yellow
— no grounding.
Description of color output signals:
green
— output is on and in working condition, load is connected;
blue
— output is administratively and in fact turned on, but the load is not connected;
red
— the output was disconnected due to input overload, overcurrent, short circuit at the
output, overvoltage at the output (accompanied by appropriate messages);
yellow
— output is on, but has an overload condition (accompanied by corresponding
messages);
38