4. Description of the RPCM Device
You can use one type of monitoring, as well as two, three or all four simultaneously. To do this,
you need to activate appropriate check boxes.
When the desired monitoring type is activated, fields with parameters specific for this particular
test type appear.
Figure 4.11.16 shows the fields for configuration of the watchdogs based on consumption and
TCP port monitoring.
Figure 4.11.16. Configuring watchdog tests based on consumption and TCP port monitoring.
To configure consumption monitoring, you need to enter parameters in the following
fields:
Consumption alarm limit, mA
— the bottom threshold of the current consumption
value, reaching of which triggers an alarm;
Consumption alarm limit, s
— stabilization delay in seconds for alarm;
Consumption restart limit, mA
— the bottom threshold of the current consumption
value, reaching of which triggers a restart;
Consumption restart limit, c
— stabilization delay in seconds for restart.