6. Command Reference of RPCM CLI
6.9.2 Command
set output name
This command set an outlet name.
Example of use:
set output 0 name "Out-0"
The return is:
Description for Output 0 has been updated
Type 'help' to get suggestions
6.9.3 Command
set output
off
It administratively disables the specified outlet from
0
to
9
.
Example of use:
set output 9 off
The return is:
[Output 9]: ON <admin: ON> 0mA 0W
6.9.4 Command
set output
on
It administratively includes the specified outlet from
0
to
9
.
Example of use:
set output 9 on
The return is:
[Output 9]: ON <admin: ON> 0mA 0W
6.9.5 Command
set output
overcurrent
it allows you to control power current consumption.
It is possible to set the threshold value for pre-alarm
alarm
and then turn off.
The available options are:
alarm
,
turn off
,
help
Help ask:
set output 9 overcurrent ?
The return is:
RPCM Commands description:
set output 0-9 overcurrent alarm - tune overcurrent alarm limits
set output 0-9 overcurrent turn off - tune overcurrent turn off limits
set output 0-9 overcurrent help - show this help
Type 'help' to get suggestions
306