2. Installing RPCM
2.2.7.2. Connecting wires to the inputs RPCM DC 232A
To connect the input to the electrical circuit use two terminals with screws for the positive and
negative conductors.
To connect cable to the screw terminal:
Remove insulation from wire.
Insert the wire into the contact hole.
Insert the hex key into the side hole to tighten the screw.
Tighten the screw with a force of 10 Nm ... 12 Nm.
Connect the second conductor in the same way.
Figure 2.2.6. Connect the conductor to the input terminal of RPCM DC 232A.
2.2.7.3. Connection of conductors to RPCM DC ATS 76A and RPCM
DC 232A output clamp terminals
RPCM DC uses clamp terminals to connect power wires to supply power to loads.
To connect the conductor to the RPCM DC ATS 76A outlet and RPCM DC 232A outlet, you must:
Remove the insulation from the conductor.
To open the clamp, press the orange button with a screwdriver.
Insert the conductor directly into the round hole of the terminal.
Remove the screwdriver releasing the button and make sure that the conductor sits in the termi-
nal firmly.Similarly connect the second conductor.To remove the conductor, you also need to push
in the orange button with a screwdriver, remove the conductor and release the button.