6. Command Reference of RPCM CLI
6.9.5.1. Command
set output
overcurrent
alarm limit
Available level 1 parameters indicating current units are:
amps
,
milliamps
, and time unit seconds`
for the delay parameter of the signal.
Available are level 2 parameters, indicating the numerical values of the parameters.
Help ask:
set output 9 overcurrent alarm limit
The return is:
RPCM Commands description:
set output 0-9 overcurrent
alarm limit amps 0.000-10.000 - set limit in amps
set output 0-9 overcurrent
alarm limit milliamps 0-10000 - set limit in milliamps
set output 0-9 overcurrent
alarm limit seconds 0-65535 - set alarm confirmation
delay in seconds
set output 0-9 overcurrent
alarm limit help - show this help
Example 1
. Setting alarm outlet limit to 9A to outlet
9
.
Command:
set output 9 overcurrent alarm limit amps 9.00
The return is:
New overcurrent alarm limit for output 9 is 9.0 amps (was 9.5 amps)
Example 2.
Setting the delay for the alarm limit in 5 seconds for the outlet
9.
Command
:
set output 9 overcurrent alarm limit seconds 5
The return is:
New overcurrent alarm limit confirmation delay for output 9 is 5 seconds (was 30 seconds)
6.9.5.2. Command
set output
overcurrent
turn off limit
Available level 1 parameters indicating current units are:
amps
,
milliamps
, and time unit seconds`
for the delay parameter of the signal.
Available level 2 parameters indicating the numerical values of the parameters of level 1.
Help ask:
set output 9 overcurrent turn off limit ?
307