Page 174
Common Parameters
P216, P226, P236, P246, P256 - Relay Allocation
This parameter determines which input the relay will act on. You can set it
to the transducer (default), or the optional auxiliary (current) input, or an
average of the two. In most cases, this will not need to be changed from the
default.
Option
Description
1= Xducer 1 (Default)
Relay acts on Xducer 1calculated levels.
2= Xducer 2
Relay acts on Xducer 2 calculated levels.
3 = Auxiliary (Optional)
Relay acts on optional current input levels
When Ultra Wizard = 1 Level/Volume or 2 Pump/Differential
4 = Average of 1 & 2
Relay acts on the resulting average levels
of two signal inputs.
When Ultra Wizard = 2 Pump/Differential
5 = Differential of 1 & 2
Relay acts on the resulting differential
level of two signal inputs.
P217, P227, P 237, P247, P257 - Relay Closures
The
Ultra 5
will record how many times each relay is closed, this parameter
displays the number of times the relay has activated since the relay has been
in use. It can be reset with any value.
P218, P228, P238, P248, P258 - Relay Fail Safe
Your
Ultra 5
has a general fail-safe parameter
P808
. However, this can be
overridden so that each individual relay has its own independent fail safe
mode.
This parameter determines what the relay will do in the event of the
Failsafe
Time
(
P809
) expiring.
Option
Description
0 = Default
Relay assumes system default mode P808
1 = Hold
Relay remains in its current state
2 = De-Energise
Relay will De-Energise
3 = Energise
Relay will Energise
Содержание ULTRA 5
Страница 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Страница 16: ...Page 8 Fascia Mount ...
Страница 17: ...Page 9 Rack and Panel ...
Страница 18: ...Page 10 This page left blank intentionally ...
Страница 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Страница 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Страница 25: ...Page 17 Dimensions of the panel enclosure are as shown below VOLTAGE SELECTOR AC POWER FUSE 230 115 ...
Страница 35: ...Page 27 This page left blank intentionally ...
Страница 151: ...Page 143 This page left blank intentionally ...
Страница 240: ...Page 232 This page left blank intentionally ...