Example 2 Sump Control (pump down)
A sump is typically used to temporarily hold water or effluent, and when the
level reaches a specific point, the sump is pumped down, with the fluid
being transferred to another process.
empty distance (P105), 3.5m
100%, span (P106), 2.8m
85% , high alarm on (P253), 2.38m
80% , high alarm off (P254), 2.24m
20% , pump 1+2 off (P214, 224), 0.56m
0% , empty level
50%, pump 2 on (P 223), 1.4m
30%, pump 1 on (P 213), 0 .84m
In this example, there are two pumps, which will be set to
alternate duty
assist
, so they come on alternately. Pump 1 is to be set to relay 1, pump 2 to
relay 2, and the high-level alarm to relay 5.
This will operate as follows. During normal operation,
pump 1
will come
on at 0.84 m, and pump down to 0.56 m. The setpoints are then shifted to
pump 2
, which will come on first next time.
During peak periods, when
pump 1
cannot cope,
pump 1
will come on at
0.84 m,
pump 2
will come on at 1.4 m, and pump down to 0.56 m. The
setpoints are then shifted to
pump 2
, which will come on
first next time
.
If neither pump can cope, and the level rises to 2.38 m, then the alarm relay
(relay 5) will come on, and go off when the level falls to 2.24 m. This will
indicate insufficient capacity of the pumps.
The display will show the level in the sump and the mA output will be
representative of level where 4mA = empty level (0%) and 20mA = 2.8m
(100%)
Содержание ULTRA 5
Страница 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Страница 16: ...Page 8 Fascia Mount ...
Страница 17: ...Page 9 Rack and Panel ...
Страница 18: ...Page 10 This page left blank intentionally ...
Страница 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Страница 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Страница 25: ...Page 17 Dimensions of the panel enclosure are as shown below VOLTAGE SELECTOR AC POWER FUSE 230 115 ...
Страница 35: ...Page 27 This page left blank intentionally ...
Страница 151: ...Page 143 This page left blank intentionally ...
Страница 240: ...Page 232 This page left blank intentionally ...