Example 3 Volume Application
A cylindrical tank with a diameter of 2m and a flat base that is typically
used to temporarily hold liquid, and you wish to know the volume of liquid.
You also require a high and low alarm and when the level reaches a specific
point, the vessel is pumped down, with the fluid being transferred to another
process.
empty distance (P105), 3.5m
100%, span (P106), 2.8m
85%, high alarm on (P243), 2.38m
80%, high alarm off (P244), 2.24m
80%, control (down) on (P213), 2.24m
15% , low alarm off (P254), 0.42m
10%, low alarm on (P253), 0.28m
0%, empty level
20%, control (down) off (P214), 0.7m
In this example, there is a pump (relay 1), which will come on if the level
rises to 2.24 m, and go off when the level drops to 0.7 m. (
control down
). If
the level rises to 2.4 m, then the high-level alarm (relay 4) will come on
until the level drops to 2.24 m. If the level falls to 0.28m, then the low-level
alarm (relay 5) will come on until the level rises to 0.42 m.
The display will show the volume of fluid in the tank and the mA output
will be representative of Volume where 4mA = empty (0%) and 20mA =
Max Volume (100%).
Содержание ULTRA 5
Страница 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Страница 16: ...Page 8 Fascia Mount ...
Страница 17: ...Page 9 Rack and Panel ...
Страница 18: ...Page 10 This page left blank intentionally ...
Страница 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Страница 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Страница 25: ...Page 17 Dimensions of the panel enclosure are as shown below VOLTAGE SELECTOR AC POWER FUSE 230 115 ...
Страница 35: ...Page 27 This page left blank intentionally ...
Страница 151: ...Page 143 This page left blank intentionally ...
Страница 240: ...Page 232 This page left blank intentionally ...