P192 Demote Flags
This parameter will indicate, in a binary number format as detailed below,
which pumps, if any, have been demoted. Any demoted pump(s) can be
reset by entering “0”.
0 = None
16 = Pump 5
1 = Pump 1
17 = Pump 1 + 5
2 = Pump 2
18 = Pump 2 + 5
3 = Pump 1 + 2
19 = Pump 1 + 2 + 5
4 = Pump 3
20 = Pump 3 + 5
5 = Pump 1 + 3
21 = Pump 1 + 3 + 5
6 = Pump 2 + 3
22 = Pump 2 + 3 +5
7 = Pump 1 + 2 + 3
23 = Pump 1 + 2 + 3 + 5
8 = Pump 4
24 = Pump 4 + 5
9 = Pump 1 + 4
25 = Pump 1 + 4 + 5
10 = Pump 2 + 4
26 = Pump 2 + 4 + 5
11 = Pump 1 + 2 + 4
27 = Pump 1 + 2 + 4 + 5
12 = Pump 3 + 4
28 = Pump 3 + 4 + 5
13 = Pump 1 + 3 + 4
29 = Pump 1 + 3 + 4 + 5
14 = Pump 2 + 3+ 4
30 = Pump 2 + 3 + 4 + 5
15 = Pump 1 + 2 + 3 + 4
31 = Pump 1 + 2 + 3 + 4 + 5
P193 Calib. Pumps
This parameter is used to calibrate the pumps and determine the optimum
(100%) efficiency of the pump from which all subsequent efficiency
calculations will be derived. You can either choose to “calibrate” an
individual pump or alternatively have each pump “calibrated” in turn
automatically.
When selecting pumps to be calibrated individually (Option 1 to 5), it is
essential that the level in the vessel is above the relevant pump start point to
ensure correct calibration. Once you have selected the pump to be
“calibrated” you will be prompted to return to the RUN mode, there will
then be a delay before the pump starts which is equal to the
Calib. Delay
(
P188
) the display will show the time being counted down time to the pump
start. Once the pump has started the display will show a countdown time
equal to the
Cal. Duration
(
P189
), calculation of pump efficiency will be
complete on the expiry of the count and the unit will return to normal
operation.
If you choose to “calibrate” the pumps automatically (Option 7) then when
the unit is returned to the RUN mode each pump will be “calibrated” in turn
as and when it is next called to run.
Содержание ULTRA 5
Страница 1: ...ULTRA 5 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 15: ...Page 7 EU Declaration of Conformity Wall Mount ...
Страница 16: ...Page 8 Fascia Mount ...
Страница 17: ...Page 9 Rack and Panel ...
Страница 18: ...Page 10 This page left blank intentionally ...
Страница 21: ...Page 13 The full dimensions of the enclosure are as shown below ...
Страница 23: ...Page 15 The full dimensions of the Fascia mount enclosure are as shown below ...
Страница 25: ...Page 17 Dimensions of the panel enclosure are as shown below VOLTAGE SELECTOR AC POWER FUSE 230 115 ...
Страница 35: ...Page 27 This page left blank intentionally ...
Страница 151: ...Page 143 This page left blank intentionally ...
Страница 240: ...Page 232 This page left blank intentionally ...